Skip to Content

Dry cooler BC/BD-163BB1-B19 C

Dry cooler BC/BD-163BB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-163BB1-B19 C

Heat rejection i
30.30 kW
Air flow
11,701 m³/h
Fans
1 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 11,701 m³/h
External surface 69.6 m²
Inner volume 9.7 dm³
Fin materialAluminium
Net weight 125 kg
Fans
Quantity 1
Diameter 630 mm
Speed 1,330 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 52.0 dB(A)
Sound power 83.4 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
BC/BD-163BB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
30.295 kW Fluid flow 5.26 m³/h Pressure drop 102.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
25.845 kW Fluid flow 4.49 m³/h Pressure drop 77.7 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 17.33 not rated not rated not rated not rated not rated
40 30.30 17.41 not rated not rated not rated not rated
45 43.00 30.31 17.48 not rated not rated not rated
50 55.63 42.95 30.32 17.55 not rated not rated
55 68.21 55.52 42.91 30.34 17.61 not rated
60 80.78 68.04 55.42 42.89 30.37 17.68

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.86 not rated not rated not rated not rated not rated
40 25.85 14.93 not rated not rated not rated not rated
45 36.59 25.85 14.99 not rated not rated not rated
50 47.26 36.54 25.86 15.04 not rated not rated
55 57.90 47.16 36.51 25.87 15.10 not rated
60 68.52 57.75 47.08 36.49 25.90 15.16

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 30.295 5.26 102.8
Low speed (Y) 25.845 4.49 77.7

Dimensions

Dimension drawing of BC/BD-163BB1-B19 C
Dimension drawing
Dimensions as drawn
A 1250 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 1180 mm
K 1500 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 1250 mm
Width 1230 mm
Height 1220 mm

Downloads