BC/BD-163BD1-B01 C
30.11 kW
Defrost: None
Product code: BC/BD-t-180GC5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 7,440 m³/h |
|---|---|
| External surface | 92.0 m² |
| Inner volume | 13.0 dm³ |
| Fin material | Aluminium |
| Net weight | 182 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 32.0 dB(A) |
|---|---|
| Sound power | 64.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| BC/BD-t-180GC5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 17.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 30.13 | 18.01 | not rated | not rated | not rated | not rated |
| 45 | 41.91 | 30.13 | 18.09 | not rated | not rated | not rated |
| 50 | 53.56 | 41.86 | 30.16 | 18.19 | not rated | not rated |
| 55 | 65.14 | 53.45 | 41.84 | 30.21 | 18.29 | not rated |
| 60 | 76.69 | 64.98 | 53.38 | 41.86 | 30.30 | 18.40 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 13.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 22.36 | 13.53 | not rated | not rated | not rated | not rated |
| 45 | 30.92 | 22.37 | 13.60 | not rated | not rated | not rated |
| 50 | 39.36 | 30.88 | 22.39 | 13.68 | not rated | not rated |
| 55 | 47.75 | 39.29 | 30.87 | 22.44 | 13.77 | not rated |
| 60 | 56.11 | 47.64 | 39.25 | 30.91 | 22.52 | 13.88 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 30.126 | 5.22 | 31.0 |
| Low speed (Y) | 22.359 | 3.88 | 18.2 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 1700 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1700 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.