BC/BD-t-180GC5-B01 C
50.11 kW
Defrost: None
Product code: BC/BD-263CA1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 24,225 m³/h |
|---|---|
| External surface | 123.4 m² |
| Inner volume | 15.9 dm³ |
| Fin material | Aluminium |
| Net weight | 217 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-263CA1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 50.13 | 28.28 | not rated | not rated | not rated | not rated |
| 45 | 71.81 | 50.21 | 28.44 | not rated | not rated | not rated |
| 50 | 93.37 | 71.79 | 50.29 | 28.58 | not rated | not rated |
| 55 | 114.88 | 93.27 | 71.79 | 50.36 | 28.71 | not rated |
| 60 | 136.36 | 114.69 | 93.18 | 71.79 | 50.44 | 28.85 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 24.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 43.93 | 24.89 | not rated | not rated | not rated | not rated |
| 45 | 62.78 | 43.99 | 25.03 | not rated | not rated | not rated |
| 50 | 81.52 | 62.76 | 44.06 | 25.16 | not rated | not rated |
| 55 | 100.22 | 81.43 | 62.75 | 44.12 | 25.28 | not rated |
| 60 | 118.88 | 100.04 | 81.35 | 62.76 | 44.20 | 25.40 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 50.133 | 8.70 | 76.8 |
| Low speed (Y) | 43.926 | 7.62 | 60.8 |
| A | 2100 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 2400 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.