BC/BD-263CA1-B19 C
50.13 kW
Defrost: None
Product code: BC/BD-2x180HB1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 16,705 m³/h |
|---|---|
| External surface | 160.7 m² |
| Inner volume | 22.0 dm³ |
| Fin material | Aluminium |
| Net weight | 311 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-2x180HB1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 50.21 | 29.09 | not rated | not rated | not rated | not rated |
| 45 | 71.00 | 50.30 | 29.26 | not rated | not rated | not rated |
| 50 | 91.62 | 71.01 | 50.39 | 29.43 | not rated | not rated |
| 55 | 112.16 | 91.56 | 71.04 | 50.51 | 29.60 | not rated |
| 60 | 132.66 | 112.03 | 91.53 | 71.11 | 50.65 | 29.78 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 22.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 39.65 | 23.12 | not rated | not rated | not rated | not rated |
| 45 | 55.85 | 39.71 | 23.26 | not rated | not rated | not rated |
| 50 | 71.91 | 55.84 | 39.76 | 23.39 | not rated | not rated |
| 55 | 87.90 | 71.83 | 55.84 | 39.84 | 23.52 | not rated |
| 60 | 103.84 | 87.76 | 71.78 | 55.88 | 39.95 | 23.67 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 50.210 | 8.71 | 47.2 |
| Low speed (Y) | 39.646 | 6.88 | 30.9 |
| A | 1400 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1150 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 1700 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1700 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.