BC/BD-263CB1-B19 C
64.22 kW
Defrost: None
Product code: BC/BD-280AC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 16,288 m³/h |
|---|---|
| External surface | 329.5 m² |
| Inner volume | 37.7 dm³ |
| Fin material | Aluminium |
| Net weight | 367 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | C |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-280AC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 38.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 64.32 | 38.88 | not rated | not rated | not rated | not rated |
| 45 | 89.13 | 64.21 | 38.93 | not rated | not rated | not rated |
| 50 | 113.70 | 88.88 | 64.15 | 39.00 | not rated | not rated |
| 55 | 138.17 | 113.33 | 88.71 | 64.14 | 39.10 | not rated |
| 60 | 162.59 | 137.68 | 113.06 | 88.63 | 64.21 | 39.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 29.97 | not rated | not rated | not rated | not rated | not rated |
| 40 | 49.12 | 30.03 | not rated | not rated | not rated | not rated |
| 45 | 67.71 | 49.07 | 30.09 | not rated | not rated | not rated |
| 50 | 86.11 | 67.57 | 49.06 | 30.17 | not rated | not rated |
| 55 | 104.43 | 85.90 | 67.50 | 49.10 | 30.29 | not rated |
| 60 | 122.71 | 104.15 | 85.78 | 67.51 | 49.21 | 30.43 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 64.322 | 11.16 | 97.4 |
| Low speed (Y) | 49.117 | 8.52 | 60.2 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 3050 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.