BC/BD-t-180JB1-B01 C
64.52 kW
Defrost: None
Product code: BC/BD-t-263AC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 15,757 m³/h |
|---|---|
| External surface | 186.1 m² |
| Inner volume | 27.6 dm³ |
| Fin material | Aluminium |
| Net weight | 223 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 77.5 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-t-263AC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 38.07 | not rated | not rated | not rated | not rated | not rated |
| 40 | 64.51 | 38.24 | not rated | not rated | not rated | not rated |
| 45 | 89.95 | 64.42 | 38.38 | not rated | not rated | not rated |
| 50 | 115.05 | 89.65 | 64.36 | 38.53 | not rated | not rated |
| 55 | 139.99 | 114.56 | 89.41 | 64.34 | 38.70 | not rated |
| 60 | 164.84 | 139.32 | 114.17 | 89.27 | 64.40 | 38.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 64.513 | 11.19 | 23.9 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2150 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.