Skip to Content

Dry cooler BC/BD-280AC5-B01I C

Dry cooler BC/BD-280AC5-B01I C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280AC5-B01I C

Heat rejection i
92.87 kW
Air flow
31,907 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 31,907 m³/h
External surface 278.6 m²
Inner volume 44.1 dm³
Fin materialAluminium
Net weight 367 kg
Fans
Quantity 2
Diameter 800 mm
Speed 880 rpm
Power 3,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 54.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280AC5-B01I C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
92.867 kW Fluid flow 16.12 m³/h Pressure drop 26.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 52.59 not rated not rated not rated not rated not rated
40 92.87 53.00 not rated not rated not rated not rated
45 132.17 93.05 53.37 not rated not rated not rated
50 171.16 132.16 93.22 53.70 not rated not rated
55 210.00 170.97 132.18 93.42 54.03 not rated
60 248.76 209.65 170.86 132.27 93.67 54.38

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 92.867 16.12 26.6

Dimensions

Dimension drawing of BC/BD-280AC5-B01I C
Dimension drawing
Dimensions as drawn
A 2750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 2500 mm
H 1200 mm
I 1190 mm
K 3050 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2750 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.