BC/BD-2x180MB1-B01 C
124.68 kW
Defrost: None
Product code: BC/BD-280CC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 35,165 m³/h |
|---|---|
| External surface | 480.5 m² |
| Inner volume | 59.7 dm³ |
| Fin material | Aluminium |
| Net weight | 455 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 3,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 84.1 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-280CC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 73.35 | not rated | not rated | not rated | not rated | not rated |
| 40 | 124.66 | 73.49 | not rated | not rated | not rated | not rated |
| 45 | 174.62 | 124.41 | 73.62 | not rated | not rated | not rated |
| 50 | 224.14 | 174.02 | 124.21 | 73.75 | not rated | not rated |
| 55 | 273.47 | 223.22 | 173.53 | 124.07 | 73.91 | not rated |
| 60 | 322.67 | 272.22 | 222.45 | 173.17 | 124.05 | 74.14 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 124.660 | 21.64 | 61.8 |
| A | 3850 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3600 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 4150 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3850 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.