Skip to Content

Dry cooler BC/BD-2x180KC1-B01 C

Dry cooler BC/BD-2x180KC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x180KC1-B01 C

Heat rejection i
124.54 kW
Air flow
38,257 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 1 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 38,257 m³/h
External surface 357.2 m²
Inner volume 52.4 dm³
Fin materialAluminium
Net weight 405 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2x180KC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
124.540 kW Fluid flow 21.61 m³/h Pressure drop 83.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
96.994 kW Fluid flow 16.83 m³/h Pressure drop 53.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 72.87 not rated not rated not rated not rated not rated
40 124.54 73.09 not rated not rated not rated not rated
45 174.97 124.45 73.29 not rated not rated not rated
50 224.99 174.61 124.39 73.49 not rated not rated
55 274.82 224.37 174.31 124.39 73.72 not rated
60 324.56 273.95 223.85 174.13 124.48 73.99

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 57.23 not rated not rated not rated not rated not rated
40 96.99 57.38 not rated not rated not rated not rated
45 135.67 96.87 57.53 not rated not rated not rated
50 174.01 135.31 96.78 57.67 not rated not rated
55 212.19 173.43 135.03 96.75 57.84 not rated
60 250.28 211.40 172.97 134.86 96.81 58.07

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 124.540 21.61 83.8
Low speed (Y) 96.994 16.83 53.8

Dimensions

Dimension drawing of BC/BD-2x180KC1-B01 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 1850 mm
H 1750 mm
I 2260 mm
K 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2400 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.