Skip to Content

Dry cooler BC/BD-280CC5-B01I C

Dry cooler BC/BD-280CC5-B01I C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280CC5-B01I C

Heat rejection i
116.18 kW
Air flow
35,697 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 35,697 m³/h
External surface 406.3 m²
Inner volume 59.7 dm³
Fin materialAluminium
Net weight 443 kg
Fans
Quantity 2
Diameter 800 mm
Speed 880 rpm
Power 3,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 83.8 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280CC5-B01I C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
116.175 kW Fluid flow 20.16 m³/h Pressure drop 54.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 67.83 not rated not rated not rated not rated not rated
40 116.18 68.00 not rated not rated not rated not rated
45 163.36 116.02 68.15 not rated not rated not rated
50 210.17 162.91 115.89 68.31 not rated not rated
55 256.80 209.43 162.53 115.82 68.47 not rated
60 303.33 255.78 208.81 162.26 115.83 68.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 116.175 20.16 54.5

Dimensions

Dimension drawing of BC/BD-280CC5-B01I C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1190 mm
K 4150 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.