BC/BD-2X350CD5-B09 C
115.76 kW
Defrost: None
Product code: BC/BD-363BD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 32,575 m³/h |
|---|---|
| External surface | 349.0 m² |
| Inner volume | 43.0 dm³ |
| Fin material | Aluminium |
| Net weight | 332 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-363BD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 68.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.82 | 68.54 | not rated | not rated | not rated | not rated |
| 45 | 162.00 | 115.64 | 68.68 | not rated | not rated | not rated |
| 50 | 207.78 | 161.52 | 115.50 | 68.82 | not rated | not rated |
| 55 | 253.37 | 207.03 | 161.14 | 115.42 | 69.00 | not rated |
| 60 | 298.86 | 252.35 | 206.41 | 160.89 | 115.46 | 69.23 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 56.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 95.40 | 56.91 | not rated | not rated | not rated | not rated |
| 45 | 132.97 | 95.32 | 57.05 | not rated | not rated | not rated |
| 50 | 170.18 | 132.69 | 95.26 | 57.17 | not rated | not rated |
| 55 | 207.23 | 169.72 | 132.45 | 95.20 | 57.32 | not rated |
| 60 | 244.18 | 206.58 | 169.31 | 132.24 | 95.23 | 57.53 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 115.824 | 20.10 | 79.3 |
| Low speed (Y) | 95.396 | 16.54 | 56.2 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 3300 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.