Dry cooler BC/BD-280HB5-B01 C

Dry cooler BC/BD-280HB5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280HB5-B01 C

Heat rejection i
71.42 kW
Air flow
34,665 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 34,665 m³/h
External surface 137.9 m²
Inner volume 25.4 dm³
Fin materialAluminium
Net weight 312 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 52.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280HB5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
71.419 kW Fluid flow 12.40 m³/h Pressure drop 29.6 kPa
Heat rejection · Low speed (Y)
58.023 kW Fluid flow 10.07 m³/h Pressure drop 20.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 39.39 not rated not rated not rated not rated not rated
40 71.42 39.85 not rated not rated not rated not rated
45 102.79 71.74 40.25 not rated not rated not rated
50 133.97 103.01 72.03 40.61 not rated not rated
55 165.07 134.12 103.24 72.32 40.94 not rated
60 196.12 165.14 134.28 103.49 72.62 41.27

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 32.17 not rated not rated not rated not rated not rated
40 58.02 32.54 not rated not rated not rated not rated
45 83.26 58.26 32.86 not rated not rated not rated
50 108.32 83.41 58.48 33.15 not rated not rated
55 133.30 108.39 83.56 58.70 33.43 not rated
60 158.23 133.29 108.48 83.73 58.94 33.70

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 71.419 12.40 29.6
Low speed (Y) 58.023 10.07 20.5

Dimensions

Dimension drawing of BC/BD-280HB5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 1180 mm
K 2750 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2450 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.