Dry cooler BC/BD-280HC5-B01 C

Dry cooler BC/BD-280HC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280HC5-B01 C

Heat rejection i
84.72 kW
Air flow
32,098 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 2 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 32,098 m³/h
External surface 183.9 m²
Inner volume 30.5 dm³
Fin materialAluminium
Net weight 326 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 84.8 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280HC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
84.723 kW Fluid flow 14.70 m³/h Pressure drop 53.3 kPa
Heat rejection · Low speed (Y)
67.341 kW Fluid flow 11.69 m³/h Pressure drop 35.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 48.30 not rated not rated not rated not rated not rated
40 84.72 48.66 not rated not rated not rated not rated
45 120.37 84.96 48.99 not rated not rated not rated
50 155.77 120.50 85.19 49.32 not rated not rated
55 191.05 155.80 120.66 85.46 49.63 not rated
60 226.27 191.00 155.90 120.88 85.76 49.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 38.65 not rated not rated not rated not rated not rated
40 67.34 38.95 not rated not rated not rated not rated
45 95.32 67.52 39.22 not rated not rated not rated
50 123.08 95.41 67.70 39.48 not rated not rated
55 150.73 123.09 95.53 67.92 39.75 not rated
60 178.32 150.67 123.16 95.72 68.17 40.03

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 84.723 14.70 53.3
Low speed (Y) 67.341 11.69 35.5

Dimensions

Dimension drawing of BC/BD-280HC5-B01 C
Dimension drawing
Dimensions as drawn
A 2450 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 2200 mm
H 1050 mm
I 1180 mm
K 2750 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2450 mm
Width 1230 mm
Height 1450 mm

Downloads