BC/BD-2X263CA1-B01 C
84.76 kW
Defrost: None
Product code: BC/BD-t-180LC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 20,193 m³/h |
|---|---|
| External surface | 248.2 m² |
| Inner volume | 29.3 dm³ |
| Fin material | Aluminium |
| Net weight | 273 kg |
| Quantity | 1 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 1,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-180LC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 51.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 84.77 | 51.01 | not rated | not rated | not rated | not rated |
| 45 | 117.39 | 84.41 | 51.00 | not rated | not rated | not rated |
| 50 | 149.63 | 116.71 | 84.10 | 51.01 | not rated | not rated |
| 55 | 181.69 | 148.66 | 116.14 | 83.86 | 51.06 | not rated |
| 60 | 213.65 | 180.43 | 147.83 | 115.69 | 83.73 | 51.17 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 39.08 | not rated | not rated | not rated | not rated | not rated |
| 40 | 64.18 | 39.07 | not rated | not rated | not rated | not rated |
| 45 | 88.34 | 63.88 | 39.06 | not rated | not rated | not rated |
| 50 | 112.20 | 87.81 | 63.63 | 39.07 | not rated | not rated |
| 55 | 135.92 | 111.44 | 87.36 | 63.45 | 39.11 | not rated |
| 60 | 159.56 | 134.95 | 110.81 | 87.02 | 63.35 | 39.20 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 84.768 | 14.70 | 54.2 |
| Low speed (Y) | 64.178 | 11.13 | 33.0 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 2400 mm |
| I | 1180 mm |
| K | 3050 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.