Skip to Content

Dry cooler BC/BD-280MC1-B01 C

Dry cooler BC/BD-280MC1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280MC1-B01 C

Heat rejection i
142.98 kW
Air flow
41,415 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 41,415 m³/h
External surface 496.3 m²
Inner volume 57.0 dm³
Fin materialAluminium
Net weight 500 kg
Fans
Quantity 2
Diameter 800 mm
Speed 900 rpm
Power 3,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 51.0 dB(A)
Sound power 83.0 dB(A)
Energy class D
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-280MC1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
142.982 kW Fluid flow 24.82 m³/h Pressure drop 46.5 kPa
Heat rejection · Low speed (Y)
111.505 kW Fluid flow 19.34 m³/h Pressure drop 29.8 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 83.71 not rated not rated not rated not rated not rated
40 142.98 83.93 not rated not rated not rated not rated
45 200.63 142.70 84.10 not rated not rated not rated
50 257.75 199.93 142.47 84.27 not rated not rated
55 314.64 256.65 199.32 142.31 84.47 not rated
60 371.39 313.14 255.70 198.87 142.25 84.72

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 65.83 not rated not rated not rated not rated not rated
40 111.51 65.99 not rated not rated not rated not rated
45 155.81 111.26 66.13 not rated not rated not rated
50 199.65 155.21 111.05 66.26 not rated not rated
55 243.29 198.74 154.72 110.91 66.42 not rated
60 286.81 242.07 197.97 154.35 110.88 66.64

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 142.982 24.82 46.5
Low speed (Y) 111.505 19.34 29.8

Dimensions

Dimension drawing of BC/BD-280MC1-B01 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 1180 mm
K 5450 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5450 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.