Skip to Content

Dry cooler BC/BD-291GC5-B04 C

Dry cooler BC/BD-291GC5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-291GC5-B04 C

Heat rejection i
166.17 kW
Air flow
54,104 m³/h
Fans
2 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 54,104 m³/h
External surface 557.2 m²
Inner volume 81.6 dm³
Fin materialAluminium
Net weight 546 kg
Fans
Quantity 2
Diameter 910 mm
Speed 840 rpm
Power 5,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-291GC5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
166.174 kW Fluid flow 28.84 m³/h Pressure drop 23.1 kPa
Heat rejection · Low speed (Y)
133.006 kW Fluid flow 23.08 m³/h Pressure drop 15.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 94.42 not rated not rated not rated not rated not rated
40 166.17 95.03 not rated not rated not rated not rated
45 236.04 166.21 95.53 not rated not rated not rated
50 305.30 235.61 166.25 95.99 not rated not rated
55 374.29 304.42 235.24 166.33 96.45 not rated
60 443.11 372.98 303.68 234.99 166.50 96.92

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 76.22 not rated not rated not rated not rated not rated
40 133.01 76.72 not rated not rated not rated not rated
45 188.06 133.03 77.16 not rated not rated not rated
50 242.55 187.68 133.05 77.55 not rated not rated
55 296.77 241.80 187.39 133.13 77.94 not rated
60 350.85 295.69 241.21 187.20 133.30 78.36

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 166.174 28.84 23.1
Low speed (Y) 133.006 23.08 15.4

Dimensions

Dimension drawing of BC/BD-291GC5-B04 C
Dimension drawing
Dimensions as drawn
A 5150 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 4900 mm
H 2400 mm
I 1190 mm
K 5450 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5450 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.