BC/BD-291GC5-B04 C
166.17 kW
Defrost: None
Product code: BC/BD-2x280MC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,033 m³/h |
|---|---|
| External surface | 979.8 m² |
| Inner volume | 112.1 dm³ |
| Fin material | Aluminium |
| Net weight | 868 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2x280MC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 100.94 | not rated | not rated | not rated | not rated | not rated |
| 40 | 166.29 | 100.75 | not rated | not rated | not rated | not rated |
| 45 | 229.79 | 165.51 | 100.60 | not rated | not rated | not rated |
| 50 | 292.69 | 228.47 | 164.84 | 100.52 | not rated | not rated |
| 55 | 355.30 | 290.85 | 227.34 | 164.34 | 100.52 | not rated |
| 60 | 417.77 | 352.95 | 289.27 | 226.47 | 164.05 | 100.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 79.53 | not rated | not rated | not rated | not rated | not rated |
| 40 | 130.03 | 79.44 | not rated | not rated | not rated | not rated |
| 45 | 179.00 | 129.47 | 79.36 | not rated | not rated | not rated |
| 50 | 227.47 | 178.04 | 129.00 | 79.33 | not rated | not rated |
| 55 | 275.72 | 226.13 | 177.22 | 128.66 | 79.36 | not rated |
| 60 | 323.84 | 274.00 | 224.99 | 176.61 | 128.48 | 79.50 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 166.286 | 28.84 | 57.8 |
| Low speed (Y) | 130.034 | 22.55 | 37.2 |
| A | 5150 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4900 mm |
| H | 2400 mm |
| I | 2260 mm |
| K | 5450 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5450 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.