BC/BD-250BD1-B09 C
46.35 kW
Defrost: None
Product code: BC/BD-2X163CA1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 24,225 m³/h |
|---|---|
| External surface | 123.4 m² |
| Inner volume | 19.0 dm³ |
| Fin material | Aluminium |
| Net weight | 217 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-2X163CA1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 24.10 | not rated | not rated | not rated | not rated | not rated |
| 40 | 46.34 | 24.56 | not rated | not rated | not rated | not rated |
| 45 | 68.08 | 46.62 | 24.96 | not rated | not rated | not rated |
| 50 | 89.69 | 68.24 | 46.87 | 25.29 | not rated | not rated |
| 55 | 111.24 | 89.74 | 68.39 | 47.10 | 25.59 | not rated |
| 60 | 132.76 | 111.19 | 89.80 | 68.53 | 47.31 | 25.87 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 21.22 | not rated | not rated | not rated | not rated | not rated |
| 40 | 40.67 | 21.65 | not rated | not rated | not rated | not rated |
| 45 | 59.61 | 40.92 | 22.00 | not rated | not rated | not rated |
| 50 | 78.41 | 59.74 | 41.14 | 22.30 | not rated | not rated |
| 55 | 97.14 | 78.45 | 59.87 | 41.34 | 22.57 | not rated |
| 60 | 115.85 | 97.09 | 78.49 | 59.99 | 41.53 | 22.82 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 46.337 | 8.04 | 18.0 |
| Low speed (Y) | 40.668 | 7.06 | 14.2 |
| A | 1200 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1000 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 1500 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1500 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.