BC/BD-2X350BD5-B09 C
129.66 kW
Defrost: None
Product code: BC/BD-2X180CC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 38,051 m³/h |
|---|---|
| External surface | 480.3 m² |
| Inner volume | 67.8 dm³ |
| Fin material | Aluminium |
| Net weight | 447 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 83.1 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2X180CC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 74.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 129.66 | 75.29 | not rated | not rated | not rated | not rated |
| 45 | 182.92 | 129.67 | 75.64 | not rated | not rated | not rated |
| 50 | 235.66 | 182.60 | 129.69 | 75.95 | not rated | not rated |
| 55 | 288.19 | 235.03 | 182.32 | 129.74 | 76.28 | not rated |
| 60 | 340.58 | 287.25 | 234.51 | 182.15 | 129.89 | 76.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 59.02 | not rated | not rated | not rated | not rated | not rated |
| 40 | 101.09 | 59.29 | not rated | not rated | not rated | not rated |
| 45 | 141.85 | 101.01 | 59.53 | not rated | not rated | not rated |
| 50 | 182.16 | 141.47 | 100.95 | 59.76 | not rated | not rated |
| 55 | 222.28 | 181.51 | 141.17 | 100.96 | 60.01 | not rated |
| 60 | 262.26 | 221.35 | 180.98 | 140.99 | 101.06 | 60.30 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 129.662 | 22.51 | 36.3 |
| Low speed (Y) | 101.094 | 17.53 | 23.2 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.