Skip to Content

Dry cooler BC/BD-2X263BC5-B19 C

Dry cooler BC/BD-2X263BC5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X263BC5-B19 C

Heat rejection i
129.64 kW
Air flow
45,583 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 45,583 m³/h
External surface 311.2 m²
Inner volume 59.7 dm³
Fin materialAluminium
Net weight 367 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-2X263BC5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
129.635 kW Fluid flow 22.50 m³/h Pressure drop 89.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
109.628 kW Fluid flow 19.02 m³/h Pressure drop 66.3 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 75.22 not rated not rated not rated not rated not rated
40 129.64 75.46 not rated not rated not rated not rated
45 182.89 129.58 75.68 not rated not rated not rated
50 235.77 182.57 129.55 75.90 not rated not rated
55 288.48 235.20 182.32 129.57 76.12 not rated
60 341.10 287.67 234.75 182.17 129.67 76.38

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 63.94 not rated not rated not rated not rated not rated
40 109.63 64.15 not rated not rated not rated not rated
45 154.26 109.57 64.32 not rated not rated not rated
50 198.55 153.96 109.52 64.50 not rated not rated
55 242.69 198.03 153.72 109.53 64.69 not rated
60 286.74 241.95 197.61 153.58 109.61 64.93

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 129.635 22.50 89.2
Low speed (Y) 109.628 19.02 66.3

Dimensions

Dimension drawing of BC/BD-2X263BC5-B19 C
Dimension drawing
Dimensions as drawn
A 2150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 1900 mm
H 900 mm
I 2260 mm
K 2400 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 2150 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.