BC/BD-2x191BB5-B04 C
122.55 kW
Defrost: None
Product code: BC/BD-2X180CC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 35,165 m³/h |
|---|---|
| External surface | 480.3 m² |
| Inner volume | 67.8 dm³ |
| Fin material | Aluminium |
| Net weight | 447 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 3,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 84.1 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-2X180CC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 70.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 122.47 | 71.23 | not rated | not rated | not rated | not rated |
| 45 | 172.56 | 122.36 | 71.49 | not rated | not rated | not rated |
| 50 | 222.15 | 172.07 | 122.27 | 71.74 | not rated | not rated |
| 55 | 271.53 | 221.33 | 171.67 | 122.24 | 72.02 | not rated |
| 60 | 320.77 | 270.37 | 220.63 | 171.39 | 122.28 | 72.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 122.472 | 21.26 | 32.7 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 2400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 2100 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.