Skip to Content

Dry cooler BC/BD-t-480GC5-B03 C

Dry cooler BC/BD-t-480GC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-480GC5-B03 C

Heat rejection i
122.76 kW
Air flow
29,759 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 29,759 m³/h
External surface 367.8 m²
Inner volume 51.1 dm³
Fin materialAluminium
Net weight 588 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-480GC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
122.763 kW Fluid flow 21.29 m³/h Pressure drop 73.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
90.932 kW Fluid flow 15.77 m³/h Pressure drop 43.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 74.38 not rated not rated not rated not rated not rated
40 122.76 74.54 not rated not rated not rated not rated
45 169.71 122.65 74.73 not rated not rated not rated
50 216.19 169.38 122.63 74.95 not rated not rated
55 262.44 215.64 169.19 122.74 75.25 not rated
60 308.57 261.69 215.29 169.19 123.00 75.60

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 55.76 not rated not rated not rated not rated not rated
40 90.93 55.90 not rated not rated not rated not rated
45 124.96 90.87 56.05 not rated not rated not rated
50 158.63 124.74 90.88 56.25 not rated not rated
55 192.12 158.27 124.65 91.00 56.51 not rated
60 225.53 191.63 158.08 124.72 91.26 56.90

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 122.763 21.29 73.3
Low speed (Y) 90.932 15.77 43.1

Dimensions

Dimension drawing of BC/BD-t-480GC5-B03 C
Dimension drawing
Dimensions as drawn
A 4550 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 1180 mm
K 4850 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4850 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.