Skip to Content

Dry cooler BC/BD-380NB1-B03 C

Dry cooler BC/BD-380NB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-380NB1-B03 C

Heat rejection i
122.90 kW
Air flow
31,660 m³/h
Fans
3 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 31,660 m³/h
External surface 741.3 m²
Inner volume 86.6 dm³
Fin materialAluminium
Net weight 720 kg
Fans
Quantity 3
Diameter 800 mm
Speed 435 rpm
Power 1,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 37.0 dB(A)
Sound power 69.0 dB(A)
Energy class B
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-380NB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
122.902 kW Fluid flow 21.31 m³/h Pressure drop 87.3 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
97.884 kW Fluid flow 16.98 m³/h Pressure drop 58.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 74.28 not rated not rated not rated not rated not rated
40 122.90 74.14 not rated not rated not rated not rated
45 170.30 122.36 74.02 not rated not rated not rated
50 217.27 169.37 121.89 73.94 not rated not rated
55 264.06 215.98 168.57 121.52 73.90 not rated
60 310.74 262.40 214.87 167.94 121.29 73.97

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 59.63 not rated not rated not rated not rated not rated
40 97.88 59.50 not rated not rated not rated not rated
45 135.08 97.40 59.38 not rated not rated not rated
50 171.94 134.29 96.99 59.24 not rated not rated
55 208.63 170.83 133.60 96.57 59.14 not rated
60 245.24 207.23 169.89 132.93 96.23 59.10

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 122.902 21.31 87.3
Low speed (Y) 97.884 16.98 58.4

Dimensions

Dimension drawing of BC/BD-380NB1-B03 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 2400 mm
I 1190 mm
K 7850 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 7850 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.