BC/BD-463CB1-B01 C
107.15 kW
Defrost: None
Product code: BC/BD-2X263BB5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 47,238 m³/h |
|---|---|
| External surface | 233.4 m² |
| Inner volume | 50.9 dm³ |
| Fin material | Aluminium |
| Net weight | 343 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X263BB5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 60.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 107.12 | 60.48 | not rated | not rated | not rated | not rated |
| 45 | 153.25 | 107.32 | 60.88 | not rated | not rated | not rated |
| 50 | 199.08 | 153.24 | 107.50 | 61.25 | not rated | not rated |
| 55 | 244.78 | 198.86 | 153.23 | 107.68 | 61.58 | not rated |
| 60 | 290.41 | 244.36 | 198.68 | 153.26 | 107.89 | 61.91 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 51.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 92.09 | 52.20 | not rated | not rated | not rated | not rated |
| 45 | 131.47 | 92.26 | 52.56 | not rated | not rated | not rated |
| 50 | 170.55 | 131.44 | 92.41 | 52.88 | not rated | not rated |
| 55 | 209.52 | 170.36 | 131.43 | 92.57 | 53.18 | not rated |
| 60 | 248.41 | 209.15 | 170.20 | 131.47 | 92.76 | 53.48 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 107.119 | 18.59 | 35.1 |
| Low speed (Y) | 92.094 | 15.98 | 26.9 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 2400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.