Skip to Content

Dry cooler BC/BD-2X263CB1-B19 C

Dry cooler BC/BD-2X263CB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X263CB1-B19 C

Heat rejection i
128.43 kW
Air flow
46,526 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 46,526 m³/h
External surface 370.7 m²
Inner volume 56.9 dm³
Fin materialAluminium
Net weight 401 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-2X263CB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
128.429 kW Fluid flow 22.29 m³/h Pressure drop 55.6 kPa
Heat rejection · Low speed (Y)
109.884 kW Fluid flow 19.07 m³/h Pressure drop 42.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 73.03 not rated not rated not rated not rated not rated
40 128.43 73.44 not rated not rated not rated not rated
45 182.66 128.50 73.79 not rated not rated not rated
50 236.51 182.44 128.57 74.11 not rated not rated
55 290.18 236.01 182.25 128.66 74.42 not rated
60 343.76 289.41 235.57 182.14 128.81 74.75

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 62.87 not rated not rated not rated not rated not rated
40 109.88 63.20 not rated not rated not rated not rated
45 155.80 109.91 63.49 not rated not rated not rated
50 201.35 155.55 109.94 63.76 not rated not rated
55 246.73 200.85 155.37 110.02 64.04 not rated
60 292.03 246.00 200.45 155.26 110.15 64.33

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 128.429 22.29 55.6
Low speed (Y) 109.884 19.07 42.1

Dimensions

Dimension drawing of BC/BD-2X263CB1-B19 C
Dimension drawing
Dimensions as drawn
A 2100 mm
B 1200 mm
C 2360 mm
F 1050 mm
G 450 mm
E 1900 mm
H 900 mm
I 2310 mm
K 2400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 2400 mm
Width 2360 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.