Skip to Content

Dry cooler BC/BD-t-363AD5-B19 C

Dry cooler BC/BD-t-363AD5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-363AD5-B19 C

Heat rejection i
128.67 kW
Air flow
31,951 m³/h
Fans
3 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 31,951 m³/h
External surface 295.6 m²
Inner volume 43.0 dm³
Fin materialAluminium
Net weight 325 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-363AD5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
128.670 kW Fluid flow 22.32 m³/h Pressure drop 79.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
103.781 kW Fluid flow 18.00 m³/h Pressure drop 54.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 77.21 not rated not rated not rated not rated not rated
40 128.67 77.25 not rated not rated not rated not rated
45 178.60 128.27 77.28 not rated not rated not rated
50 228.00 177.81 127.94 77.35 not rated not rated
55 277.17 226.84 177.15 127.73 77.50 not rated
60 326.20 275.64 225.88 176.68 127.69 77.74

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 62.86 not rated not rated not rated not rated not rated
40 103.78 62.99 not rated not rated not rated not rated
45 143.37 103.62 63.13 not rated not rated not rated
50 182.51 142.96 103.52 63.29 not rated not rated
55 221.44 181.88 142.67 103.52 63.50 not rated
60 260.27 220.60 181.42 142.54 103.65 63.79

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 128.670 22.32 79.1
Low speed (Y) 103.781 18.00 54.0

Dimensions

Dimension drawing of BC/BD-t-363AD5-B19 C
Dimension drawing
Dimensions as drawn
A 3050 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 1180 mm
K 3300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3050 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.