BC/BD-580CD1-B03 C
199.70 kW
Defrost: None
Product code: BC/BD-2X280AC1-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 62,198 m³/h |
|---|---|
| External surface | 658.9 m² |
| Inner volume | 93.1 dm³ |
| Fin material | Aluminium |
| Net weight | 671 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 7,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 89.5 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X280AC1-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 113.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 199.69 | 114.73 | not rated | not rated | not rated | not rated |
| 45 | 283.20 | 199.99 | 115.48 | not rated | not rated | not rated |
| 50 | 365.96 | 283.05 | 200.30 | 116.18 | not rated | not rated |
| 55 | 448.37 | 365.41 | 283.01 | 200.68 | 116.88 | not rated |
| 60 | 530.59 | 447.43 | 365.03 | 283.14 | 201.20 | 117.63 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 199.691 | 34.66 | 34.7 |
| A | 2750 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 2500 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 3050 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2750 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.