BC/BD-t-480GC5-B01 C
200.05 kW
Defrost: None
Product code: BC/BD-t-2X363AB5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 69,059 m³/h |
|---|---|
| External surface | 350.1 m² |
| Inner volume | 81.2 dm³ |
| Fin material | Aluminium |
| Net weight | 483 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2X363AB5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 114.29 | not rated | not rated | not rated | not rated | not rated |
| 40 | 200.03 | 114.88 | not rated | not rated | not rated | not rated |
| 45 | 283.83 | 200.09 | 115.41 | not rated | not rated | not rated |
| 50 | 367.01 | 283.41 | 200.16 | 115.89 | not rated | not rated |
| 55 | 449.89 | 366.14 | 283.08 | 200.28 | 116.38 | not rated |
| 60 | 532.60 | 448.57 | 365.42 | 282.88 | 200.51 | 116.91 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 97.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 170.11 | 98.29 | not rated | not rated | not rated | not rated |
| 45 | 240.62 | 170.12 | 98.73 | not rated | not rated | not rated |
| 50 | 310.53 | 240.19 | 170.13 | 99.13 | not rated | not rated |
| 55 | 380.17 | 309.70 | 239.84 | 170.21 | 99.54 | not rated |
| 60 | 449.66 | 378.94 | 309.01 | 239.65 | 170.39 | 100.00 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 200.033 | 34.72 | 54.9 |
| Low speed (Y) | 170.113 | 29.52 | 41.2 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.