Skip to Content

Dry cooler BC/BD-t-2X363AB5-B19 C

Dry cooler BC/BD-t-2X363AB5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X363AB5-B19 C

Heat rejection i
200.03 kW
Air flow
69,059 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 63 — Ø630 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 19 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 69,059 m³/h
External surface 350.1 m²
Inner volume 81.2 dm³
Fin materialAluminium
Net weight 483 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-2X363AB5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
200.033 kW Fluid flow 34.72 m³/h Pressure drop 54.9 kPa
Heat rejection · Low speed (Y)
170.113 kW Fluid flow 29.52 m³/h Pressure drop 41.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 114.29 not rated not rated not rated not rated not rated
40 200.03 114.88 not rated not rated not rated not rated
45 283.83 200.09 115.41 not rated not rated not rated
50 367.01 283.41 200.16 115.89 not rated not rated
55 449.89 366.14 283.08 200.28 116.38 not rated
60 532.60 448.57 365.42 282.88 200.51 116.91

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 97.79 not rated not rated not rated not rated not rated
40 170.11 98.29 not rated not rated not rated not rated
45 240.62 170.12 98.73 not rated not rated not rated
50 310.53 240.19 170.13 99.13 not rated not rated
55 380.17 309.70 239.84 170.21 99.54 not rated
60 449.66 378.94 309.01 239.65 170.39 100.00

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 200.033 34.72 54.9
Low speed (Y) 170.113 29.52 41.2

Dimensions

Dimension drawing of BC/BD-t-2X363AB5-B19 C
Dimension drawing
Dimensions as drawn
A 3150 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 2260 mm
K 3500 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 3150 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.