BC/BD-580CD5-B03 C
194.49 kW
Defrost: None
Product code: BC/BD-2X363BC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 68,374 m³/h |
|---|---|
| External surface | 466.9 m² |
| Inner volume | 94.4 dm³ |
| Fin material | Aluminium |
| Net weight | 518 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X363BC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.75 | not rated | not rated | not rated | not rated | not rated |
| 40 | 194.37 | 113.14 | not rated | not rated | not rated | not rated |
| 45 | 274.25 | 194.29 | 113.44 | not rated | not rated | not rated |
| 50 | 353.57 | 273.78 | 194.25 | 113.76 | not rated | not rated |
| 55 | 432.64 | 352.72 | 273.41 | 194.28 | 114.11 | not rated |
| 60 | 511.57 | 431.43 | 352.04 | 273.18 | 194.43 | 114.50 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 164.37 | 96.15 | not rated | not rated | not rated | not rated |
| 45 | 231.32 | 164.28 | 96.42 | not rated | not rated | not rated |
| 50 | 297.76 | 230.88 | 164.22 | 96.69 | not rated | not rated |
| 55 | 363.96 | 296.98 | 230.52 | 164.23 | 96.98 | not rated |
| 60 | 430.04 | 362.86 | 296.35 | 230.31 | 164.35 | 97.33 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 194.367 | 33.74 | 84.0 |
| Low speed (Y) | 164.372 | 28.53 | 62.5 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.