BC/BD-580CC1-B03 C
194.50 kW
Defrost: None
Product code: BC/BD-580CD5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 46,309 m³/h |
|---|---|
| External surface | 1,269.6 m² |
| Inner volume | 168.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,092 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | B |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-580CD5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 118.32 | not rated | not rated | not rated | not rated | not rated |
| 40 | 194.49 | 118.28 | not rated | not rated | not rated | not rated |
| 45 | 268.34 | 193.80 | 118.26 | not rated | not rated | not rated |
| 50 | 341.43 | 267.09 | 193.23 | 118.28 | not rated | not rated |
| 55 | 414.17 | 339.65 | 266.03 | 192.83 | 118.41 | not rated |
| 60 | 486.71 | 411.86 | 338.13 | 265.26 | 192.67 | 118.70 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.85 | 90.80 | not rated | not rated | not rated | not rated |
| 45 | 202.96 | 147.21 | 90.73 | not rated | not rated | not rated |
| 50 | 257.47 | 201.86 | 146.69 | 90.72 | not rated | not rated |
| 55 | 311.70 | 255.92 | 200.95 | 146.34 | 90.81 | not rated |
| 60 | 365.78 | 309.73 | 254.66 | 200.30 | 146.19 | 91.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 194.491 | 33.73 | 35.8 |
| Low speed (Y) | 147.853 | 25.64 | 21.9 |
| A | 9100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 9400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 9400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.