BC/BD-2x280KC5-B01 C
230.22 kW
Defrost: None
Product code: BC/BD-2X363BD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 64,879 m³/h |
|---|---|
| External surface | 688.9 m² |
| Inner volume | 107.6 dm³ |
| Fin material | Aluminium |
| Net weight | 568 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X363BD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 135.93 | not rated | not rated | not rated | not rated | not rated |
| 40 | 230.24 | 136.22 | not rated | not rated | not rated | not rated |
| 45 | 322.06 | 229.88 | 136.51 | not rated | not rated | not rated |
| 50 | 413.09 | 321.13 | 229.62 | 136.80 | not rated | not rated |
| 55 | 503.75 | 411.62 | 320.38 | 229.46 | 137.16 | not rated |
| 60 | 594.20 | 501.74 | 410.42 | 319.90 | 229.56 | 137.64 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.59 | not rated | not rated | not rated | not rated | not rated |
| 40 | 189.33 | 112.95 | not rated | not rated | not rated | not rated |
| 45 | 263.91 | 189.22 | 113.28 | not rated | not rated | not rated |
| 50 | 337.79 | 263.40 | 189.17 | 113.63 | not rated | not rated |
| 55 | 411.33 | 336.92 | 263.06 | 189.23 | 113.94 | not rated |
| 60 | 484.68 | 410.10 | 336.27 | 262.88 | 189.32 | 114.35 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 230.240 | 39.96 | 77.5 |
| Low speed (Y) | 189.327 | 32.84 | 54.8 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.