BC/BD-t-580GB1-B01 C
230.57 kW
Defrost: None
Product code: BC/BD-2X550DD1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 62,906 m³/h |
|---|---|
| External surface | 980.6 m² |
| Inner volume | 132.7 dm³ |
| Fin material | Aluminium |
| Net weight | 755 kg |
| Quantity | 10 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 7,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X550DD1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 131.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 230.50 | 132.56 | not rated | not rated | not rated | not rated |
| 45 | 325.91 | 230.72 | 133.60 | not rated | not rated | not rated |
| 50 | 420.15 | 325.46 | 230.99 | 134.56 | not rated | not rated |
| 55 | 513.82 | 419.07 | 325.18 | 231.38 | 135.50 | not rated |
| 60 | 607.17 | 512.15 | 418.27 | 325.14 | 231.95 | 136.49 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 230.502 | 40.01 | 13.0 |
| A | 4300 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4100 mm |
| H | 800 mm |
| I | 1670 mm |
| K | 4600 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 4600 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.