BC/BD-t-291PC5-B04 C
164.78 kW
Defrost: None
Product code: BC/BD-2X363CC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 50,054 m³/h |
|---|---|
| External surface | 626.8 m² |
| Inner volume | 101.6 dm³ |
| Fin material | Aluminium |
| Net weight | 600 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 82.1 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.07 | not rated | not rated | not rated | not rated | not rated |
| 40 | 164.84 | 95.57 | not rated | not rated | not rated | not rated |
| 45 | 232.73 | 164.83 | 96.01 | not rated | not rated | not rated |
| 50 | 299.99 | 232.29 | 164.86 | 96.42 | not rated | not rated |
| 55 | 366.97 | 299.16 | 231.96 | 164.94 | 96.85 | not rated |
| 60 | 433.77 | 365.74 | 298.50 | 231.77 | 165.15 | 97.32 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 164.844 | 28.61 | 26.8 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.