Skip to Content

Dry cooler BC/BD-391LB5-B04 C

Dry cooler BC/BD-391LB5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-391LB5-B04 C

Heat rejection i
165.24 kW
Air flow
79,040 m³/h
Fans
3 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 79,040 m³/h
External surface 344.8 m²
Inner volume 51.9 dm³
Fin materialAluminium
Net weight 575 kg
Fans
Quantity 3
Diameter 910 mm
Speed 840 rpm
Power 8,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 63.0 dB(A)
Sound power 95.3 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-391LB5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
165.242 kW Fluid flow 28.68 m³/h Pressure drop 18.0 kPa
Heat rejection · Low speed (Y)
134.513 kW Fluid flow 23.35 m³/h Pressure drop 12.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 89.26 not rated not rated not rated not rated not rated
40 165.24 90.57 not rated not rated not rated not rated
45 239.32 166.01 91.68 not rated not rated not rated
50 312.89 239.74 166.69 92.63 not rated not rated
55 386.21 312.99 240.13 167.33 93.51 not rated
60 459.41 386.04 313.13 240.55 167.97 94.33

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 72.90 not rated not rated not rated not rated not rated
40 134.51 74.05 not rated not rated not rated not rated
45 194.25 135.15 75.02 not rated not rated not rated
50 253.48 194.60 135.73 75.86 not rated not rated
55 312.48 253.57 194.94 136.29 76.62 not rated
60 371.35 312.34 253.70 195.31 136.86 77.34

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 165.242 28.68 18.0
Low speed (Y) 134.513 23.35 12.4

Dimensions

Dimension drawing of BC/BD-391LB5-B04 C
Dimension drawing
Dimensions as drawn
A 5600 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 5350 mm
H 1750 mm
I 1180 mm
K 5900 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 5900 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.