BC/BD-391LB5-B04 C
165.24 kW
Defrost: None
Product code: BC/BD-2X550CB1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 65,248 m³/h |
|---|---|
| External surface | 478.0 m² |
| Inner volume | 80.8 dm³ |
| Fin material | Aluminium |
| Net weight | 584 kg |
| Quantity | 10 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 7,100 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X550CB1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 89.20 | not rated | not rated | not rated | not rated | not rated |
| 40 | 165.42 | 90.56 | not rated | not rated | not rated | not rated |
| 45 | 239.70 | 166.24 | 91.73 | not rated | not rated | not rated |
| 50 | 313.38 | 240.14 | 167.00 | 92.77 | not rated | not rated |
| 55 | 386.80 | 313.49 | 240.58 | 167.73 | 93.73 | not rated |
| 60 | 460.06 | 386.58 | 313.66 | 241.08 | 168.48 | 94.66 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 165.416 | 28.71 | 12.8 |
| A | 3550 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3350 mm |
| H | 650 mm |
| I | 1670 mm |
| K | 3850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3850 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.