BC/BD-2X463CC5-B01 C
223.74 kW
Defrost: None
Product code: BC/BD-2X363CD5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 65,826 m³/h |
|---|---|
| External surface | 783.5 m² |
| Inner volume | 120.8 dm³ |
| Fin material | Aluminium |
| Net weight | 648 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X363CD5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 129.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 223.74 | 130.01 | not rated | not rated | not rated | not rated |
| 45 | 315.46 | 223.64 | 130.56 | not rated | not rated | not rated |
| 50 | 406.30 | 314.77 | 223.57 | 131.05 | not rated | not rated |
| 55 | 496.77 | 405.03 | 314.18 | 223.60 | 131.57 | not rated |
| 60 | 587.01 | 494.95 | 403.96 | 313.76 | 223.79 | 132.18 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 108.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 186.58 | 109.24 | not rated | not rated | not rated | not rated |
| 45 | 262.02 | 186.45 | 109.69 | not rated | not rated | not rated |
| 50 | 336.68 | 261.35 | 186.33 | 110.11 | not rated | not rated |
| 55 | 410.98 | 335.53 | 260.83 | 186.37 | 110.58 | not rated |
| 60 | 485.08 | 409.36 | 334.60 | 260.53 | 186.55 | 111.11 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 223.737 | 38.84 | 34.3 |
| Low speed (Y) | 186.584 | 32.38 | 24.7 |
| A | 3000 mm |
|---|---|
| B | 1200 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2310 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3300 mm |
|---|---|
| Width | 2360 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.