BC/BD-2X463CC5-B01 C
223.74 kW
Defrost: None
Product code: BC/BD-780AC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 57,007 m³/h |
|---|---|
| External surface | 1,153.1 m² |
| Inner volume | 132.7 dm³ |
| Fin material | Aluminium |
| Net weight | 1,165 kg |
| Quantity | 7 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 2,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.5 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-780AC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 134.36 | not rated | not rated | not rated | not rated | not rated |
| 40 | 223.75 | 134.61 | not rated | not rated | not rated | not rated |
| 45 | 310.66 | 223.44 | 134.88 | not rated | not rated | not rated |
| 50 | 396.74 | 309.88 | 223.28 | 135.16 | not rated | not rated |
| 55 | 482.44 | 395.51 | 309.33 | 223.30 | 135.60 | not rated |
| 60 | 567.92 | 480.76 | 394.61 | 309.11 | 223.59 | 136.20 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 103.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 170.96 | 104.02 | not rated | not rated | not rated | not rated |
| 45 | 236.11 | 170.85 | 104.30 | not rated | not rated | not rated |
| 50 | 300.59 | 235.70 | 170.87 | 104.66 | not rated | not rated |
| 55 | 364.76 | 299.90 | 235.49 | 171.05 | 105.10 | not rated |
| 60 | 428.75 | 363.79 | 299.49 | 235.55 | 171.46 | 105.65 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 223.747 | 38.81 | 62.0 |
| Low speed (Y) | 170.958 | 29.65 | 38.4 |
| A | 8750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 9050 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 9050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.