BC/BD-2X563BB1-B19 C
301.34 kW
Defrost: None
Product code: BC/BD-2X380AC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 98,222 m³/h |
|---|---|
| External surface | 988.4 m² |
| Inner volume | 144.7 dm³ |
| Fin material | Aluminium |
| Net weight | 969 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.5 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X380AC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 166.71 | not rated | not rated | not rated | not rated | not rated |
| 40 | 301.32 | 168.85 | not rated | not rated | not rated | not rated |
| 45 | 431.87 | 302.49 | 170.71 | not rated | not rated | not rated |
| 50 | 561.13 | 432.36 | 303.60 | 172.40 | not rated | not rated |
| 55 | 689.79 | 561.00 | 432.93 | 304.79 | 174.02 | not rated |
| 60 | 818.11 | 689.07 | 561.10 | 433.72 | 306.10 | 175.65 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 132.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 237.87 | 134.59 | not rated | not rated | not rated | not rated |
| 45 | 339.05 | 238.73 | 136.10 | not rated | not rated | not rated |
| 50 | 438.97 | 339.31 | 239.56 | 137.48 | not rated | not rated |
| 55 | 538.33 | 438.71 | 339.65 | 240.47 | 138.80 | not rated |
| 60 | 637.40 | 537.63 | 438.71 | 340.25 | 241.52 | 140.16 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 301.323 | 52.30 | 17.3 |
| Low speed (Y) | 237.874 | 41.28 | 11.2 |
| A | 3950 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3700 mm |
| H | 1200 mm |
| I | 2310 mm |
| K | 4250 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3950 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.