Skip to Content

Dry cooler BC/BD-2X563BB1-B19 C

Dry cooler BC/BD-2X563BB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X563BB1-B19 C

Heat rejection i
301.34 kW
Air flow
116,700 m³/h
Fans
10 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 116,700 m³/h
External surface 688.9 m²
Inner volume 107.6 dm³
Fin materialAluminium
Net weight 776 kg
Fans
Quantity 10
Diameter 630 mm
Speed 1,330 rpm
Power 12,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.1 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X563BB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
301.336 kW Fluid flow 52.30 m³/h Pressure drop 74.2 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
257.014 kW Fluid flow 44.61 m³/h Pressure drop 56.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 172.10 not rated not rated not rated not rated not rated
40 301.34 172.95 not rated not rated not rated not rated
45 427.95 301.48 173.70 not rated not rated not rated
50 553.75 427.48 301.63 174.39 not rated not rated
55 679.14 552.68 427.11 301.85 175.07 not rated
60 804.33 677.51 551.81 426.91 302.21 175.78

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.49 not rated not rated not rated not rated not rated
40 257.01 148.24 not rated not rated not rated not rated
45 364.10 257.10 148.87 not rated not rated not rated
50 470.40 363.64 257.21 149.46 not rated not rated
55 576.36 469.43 363.29 257.39 150.04 not rated
60 682.11 574.89 468.65 363.12 257.71 150.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 301.336 52.30 74.2
Low speed (Y) 257.014 44.61 56.0

Dimensions

Dimension drawing of BC/BD-2X563BB1-B19 C
Dimension drawing
Dimensions as drawn
A 4950 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 4600 mm
H 900 mm
I 2260 mm
K 5300 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4950 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.