Skip to Content

Dry cooler BC/BD-2x291LD5-B04 C

Dry cooler BC/BD-2x291LD5-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x291LD5-B04 C

Heat rejection i
301.57 kW
Air flow
95,774 m³/h
Fans
4 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 95,774 m³/h
External surface 756.5 m²
Inner volume 127.2 dm³
Fin materialAluminium
Net weight 789 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 65.0 dB(A)
Sound power 97.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x291LD5-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
301.566 kW Fluid flow 52.34 m³/h Pressure drop 73.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
233.537 kW Fluid flow 40.53 m³/h Pressure drop 46.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 175.90 not rated not rated not rated not rated not rated
40 301.57 176.55 not rated not rated not rated not rated
45 424.27 301.53 177.17 not rated not rated not rated
50 546.02 423.63 301.61 177.79 not rated not rated
55 667.32 544.82 423.24 301.83 178.47 not rated
60 788.37 665.57 543.99 423.15 302.27 179.26

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 137.40 not rated not rated not rated not rated not rated
40 233.54 137.93 not rated not rated not rated not rated
45 327.12 233.51 138.43 not rated not rated not rated
50 419.86 326.63 233.57 138.95 not rated not rated
55 512.23 418.94 326.30 233.77 139.51 not rated
60 604.40 510.90 418.29 326.25 234.18 140.19

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 301.566 52.34 73.8
Low speed (Y) 233.537 40.53 46.9

Dimensions

Dimension drawing of BC/BD-2x291LD5-B04 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 2260 mm
K 4150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4150 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.