BC/BD-2x380OD5-B03 C
265.83 kW
Defrost: None
Product code: BC/BD-2X380HC1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 92,514 m³/h |
|---|---|
| External surface | 643.0 m² |
| Inner volume | 103.2 dm³ |
| Fin material | Aluminium |
| Net weight | 836 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.4 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2X380HC1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 148.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 265.61 | 150.53 | not rated | not rated | not rated | not rated |
| 45 | 379.25 | 266.66 | 151.99 | not rated | not rated | not rated |
| 50 | 491.91 | 379.86 | 267.67 | 153.35 | not rated | not rated |
| 55 | 604.13 | 492.15 | 380.56 | 268.73 | 154.67 | not rated |
| 60 | 716.09 | 604.01 | 492.58 | 381.44 | 269.94 | 156.02 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 117.79 | not rated | not rated | not rated | not rated | not rated |
| 40 | 208.65 | 119.15 | not rated | not rated | not rated | not rated |
| 45 | 296.61 | 209.44 | 120.35 | not rated | not rated | not rated |
| 50 | 383.67 | 297.03 | 210.21 | 121.47 | not rated | not rated |
| 55 | 470.32 | 383.78 | 297.54 | 211.05 | 122.56 | not rated |
| 60 | 556.73 | 470.14 | 384.07 | 298.23 | 212.03 | 123.68 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 265.605 | 46.09 | 27.8 |
| Low speed (Y) | 208.646 | 36.21 | 18.1 |
| A | 3500 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 3250 mm |
| H | 1050 mm |
| I | 2260 mm |
| K | 3800 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3500 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.