BC/BD-2X380HC1-B01 C
265.61 kW
Defrost: None
Product code: BC/BD-2x380OD5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,686 m³/h |
|---|---|
| External surface | 1,985.7 m² |
| Inner volume | 437.1 dm³ |
| Fin material | Aluminium |
| Net weight | 1,554 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-2x380OD5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 166.77 | not rated | not rated | not rated | not rated | not rated |
| 40 | 265.83 | 166.01 | not rated | not rated | not rated | not rated |
| 45 | 362.27 | 264.14 | 165.36 | not rated | not rated | not rated |
| 50 | 457.88 | 359.73 | 262.71 | 164.87 | not rated | not rated |
| 55 | 553.12 | 454.51 | 357.58 | 261.61 | 164.57 | not rated |
| 60 | 648.15 | 548.94 | 451.67 | 355.91 | 260.87 | 164.57 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 126.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 199.59 | 125.77 | not rated | not rated | not rated | not rated |
| 45 | 270.86 | 198.28 | 125.26 | not rated | not rated | not rated |
| 50 | 341.53 | 268.91 | 197.18 | 124.94 | not rated | not rated |
| 55 | 411.94 | 338.98 | 267.29 | 196.45 | 124.84 | not rated |
| 60 | 482.21 | 408.78 | 336.84 | 266.18 | 196.10 | 124.98 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 265.828 | 46.11 | 97.0 |
| Low speed (Y) | 199.586 | 34.62 | 58.4 |
| A | 7550 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7300 mm |
| H | 2400 mm |
| I | 2310 mm |
| K | 7850 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 7850 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.