Dry cooler BC/BD-2x480CB5-B03 C

Dry cooler BC/BD-2x480CB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480CB5-B03 C

Heat rejection i
266.29 kW
Air flow
80,485 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 80,485 m³/h
External surface 1,218.8 m²
Inner volume 191.5 dm³
Fin materialAluminium
Net weight 1,357 kg
Fans
Quantity 8
Diameter 800 mm
Speed 435 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 41.0 dB(A)
Sound power 73.0 dB(A)
Energy class C
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x480CB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
266.288 kW Fluid flow 46.21 m³/h Pressure drop 34.4 kPa
Heat rejection · Low speed (Y)
212.623 kW Fluid flow 36.90 m³/h Pressure drop 23.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 155.77 not rated not rated not rated not rated not rated
40 266.29 156.16 not rated not rated not rated not rated
45 374.05 265.88 156.50 not rated not rated not rated
50 480.90 372.93 265.55 156.83 not rated not rated
55 587.34 479.11 372.00 265.34 157.21 not rated
60 693.54 584.90 477.61 371.31 265.34 157.69

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 125.36 not rated not rated not rated not rated not rated
40 212.62 125.75 not rated not rated not rated not rated
45 297.43 212.41 126.11 not rated not rated not rated
50 381.48 296.70 212.26 126.47 not rated not rated
55 465.16 380.27 296.14 212.22 126.88 not rated
60 548.64 463.48 379.31 295.81 212.39 127.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 266.288 46.21 34.4
Low speed (Y) 212.623 36.90 23.0

Dimensions

Dimension drawing of BC/BD-2x480CB5-B03 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1750 mm
I 2310 mm
K 7650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.