Skip to Content

Dry cooler BC/BD-680AB1-B01 C

Dry cooler BC/BD-680AB1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680AB1-B01 C

Heat rejection i
266.50 kW
Air flow
105,651 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 6 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 01 — fan motor code; supply/poles vary with diameter

Data

Coil
Air flow 105,651 m³/h
External surface 741.3 m²
Inner volume 99.6 dm³
Fin materialAluminium
Net weight 962 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680AB1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
266.502 kW Fluid flow 46.25 m³/h Pressure drop 19.0 kPa
Heat rejection · Low speed (Y)
215.545 kW Fluid flow 37.41 m³/h Pressure drop 12.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 145.29 not rated not rated not rated not rated not rated
40 266.50 147.23 not rated not rated not rated not rated
45 384.91 267.71 148.89 not rated not rated not rated
50 502.42 385.54 268.80 150.38 not rated not rated
55 619.55 502.58 386.20 269.88 151.78 not rated
60 736.44 619.23 502.84 386.97 271.03 153.19

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 118.46 not rated not rated not rated not rated not rated
40 215.55 120.02 not rated not rated not rated not rated
45 309.89 216.37 121.34 not rated not rated not rated
50 403.36 310.19 217.14 122.53 not rated not rated
55 496.45 403.21 310.54 217.92 123.64 not rated
60 589.31 495.86 403.19 311.01 218.77 124.76

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 266.502 46.25 19.0
Low speed (Y) 215.545 37.41 12.9

Dimensions

Dimension drawing of BC/BD-680AB1-B01 C
Dimension drawing
Dimensions as drawn
A 7550 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7300 mm
H 1200 mm
I 1190 mm
K 7850 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7550 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.