BC/BD-2X263BC1-B01 C
112.37 kW
Defrost: None
Product code: BC/BD-2X450BA1-B09 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 58,807 m³/h |
|---|---|
| External surface | 237.1 m² |
| Inner volume | 41.0 dm³ |
| Fin material | Aluminium |
| Net weight | 430 kg |
| Quantity | 8 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 5,700 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-2X450BA1-B09 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 61.87 | not rated | not rated | not rated | not rated | not rated |
| 40 | 112.37 | 62.50 | not rated | not rated | not rated | not rated |
| 45 | 161.92 | 112.74 | 63.03 | not rated | not rated | not rated |
| 50 | 211.19 | 162.09 | 113.06 | 63.51 | not rated | not rated |
| 55 | 260.35 | 211.17 | 162.24 | 113.37 | 63.95 | not rated |
| 60 | 309.43 | 260.15 | 211.17 | 162.42 | 113.69 | 64.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 112.365 | 19.50 | 33.9 |
| A | 3550 mm |
|---|---|
| B | 1220 mm |
| C | 1710 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3300 mm |
| H | 800 mm |
| I | 1660 mm |
| K | 3800 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3550 mm |
|---|---|
| Width | 1800 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.