Skip to Content

Dry cooler BC/BD-480HC1-B03 C

Dry cooler BC/BD-480HC1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480HC1-B03 C

Heat rejection i
112.27 kW
Air flow
30,890 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 30,890 m³/h
External surface 434.3 m²
Inner volume 46.9 dm³
Fin materialAluminium
Net weight 597 kg
Fans
Quantity 4
Diameter 800 mm
Speed 435 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 70.0 dB(A)
Energy class C
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-480HC1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
112.267 kW Fluid flow 19.48 m³/h Pressure drop 83.8 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
85.036 kW Fluid flow 14.75 m³/h Pressure drop 51.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 66.87 not rated not rated not rated not rated not rated
40 112.27 67.07 not rated not rated not rated not rated
45 156.48 112.25 67.27 not rated not rated not rated
50 200.33 156.27 112.27 67.49 not rated not rated
55 243.99 199.94 156.17 112.38 67.76 not rated
60 287.55 243.43 199.70 156.20 112.62 68.10

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 51.12 not rated not rated not rated not rated not rated
40 85.04 51.33 not rated not rated not rated not rated
45 118.00 85.10 51.54 not rated not rated not rated
50 150.64 117.95 85.22 51.78 not rated not rated
55 183.13 150.49 118.00 85.41 52.04 not rated
60 215.55 182.89 150.48 118.17 85.72 52.39

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 112.267 19.48 83.8
Low speed (Y) 85.036 14.75 51.0

Dimensions

Dimension drawing of BC/BD-480HC1-B03 C
Dimension drawing
Dimensions as drawn
A 4550 mm
B 1450 mm
C 1230 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 1180 mm
K 4850 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4850 mm
Width 1230 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.