Skip to Content

Dry cooler BC/BD-2X463BB1-B19 C

Dry cooler BC/BD-2X463BB1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X463BB1-B19 C

Heat rejection i
237.02 kW
Air flow
93,360 m³/h
Fans
8 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 93,360 m³/h
External surface 551.1 m²
Inner volume 94.4 dm³
Fin materialAluminium
Net weight 634 kg
Fans
Quantity 8
Diameter 630 mm
Speed 1,330 rpm
Power 10,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.1 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X463BB1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
237.016 kW Fluid flow 41.14 m³/h Pressure drop 39.8 kPa
Heat rejection · Low speed (Y)
202.237 kW Fluid flow 35.10 m³/h Pressure drop 30.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 133.31 not rated not rated not rated not rated not rated
40 237.02 134.32 not rated not rated not rated not rated
45 338.43 237.36 135.17 not rated not rated not rated
50 439.15 338.25 237.68 135.93 not rated not rated
55 539.54 438.47 338.12 238.02 136.65 not rated
60 639.74 538.38 437.92 338.11 238.44 137.39

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 114.29 not rated not rated not rated not rated not rated
40 202.24 115.15 not rated not rated not rated not rated
45 288.04 202.51 115.89 not rated not rated not rated
50 373.18 287.86 202.78 116.56 not rated not rated
55 458.01 372.55 287.72 203.07 117.20 not rated
60 542.67 456.97 372.05 287.70 203.44 117.85

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 237.016 41.14 39.8
Low speed (Y) 202.237 35.10 30.0

Dimensions

Dimension drawing of BC/BD-2X463BB1-B19 C
Dimension drawing
Dimensions as drawn
A 4050 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 2260 mm
K 4400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4050 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.