BC/BD-2X363CD1-B19 C
237.61 kW
Defrost: None
Product code: BC/BD-580DB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 83,282 m³/h |
|---|---|
| External surface | 586.4 m² |
| Inner volume | 113.6 dm³ |
| Fin material | Aluminium |
| Net weight | 822 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.2 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-580DB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 133.86 | not rated | not rated | not rated | not rated | not rated |
| 40 | 237.35 | 135.02 | not rated | not rated | not rated | not rated |
| 45 | 338.53 | 238.04 | 136.08 | not rated | not rated | not rated |
| 50 | 438.93 | 338.81 | 238.72 | 137.04 | not rated | not rated |
| 55 | 538.99 | 438.86 | 339.18 | 239.45 | 137.96 | not rated |
| 60 | 638.84 | 538.55 | 438.95 | 339.71 | 240.23 | 138.93 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 107.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 188.55 | 108.22 | not rated | not rated | not rated | not rated |
| 45 | 267.67 | 189.04 | 109.04 | not rated | not rated | not rated |
| 50 | 346.09 | 267.82 | 189.54 | 109.79 | not rated | not rated |
| 55 | 424.18 | 345.93 | 268.06 | 190.04 | 110.51 | not rated |
| 60 | 502.08 | 423.73 | 345.95 | 268.37 | 190.60 | 111.27 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 237.347 | 41.19 | 33.6 |
| Low speed (Y) | 188.545 | 32.72 | 22.1 |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 6650 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 6350 mm |
|---|---|
| Height | 1450 mm |