Dry cooler BC/BD-2X463BD1-B19 C

Dry cooler BC/BD-2X463BD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2X463BD1-B19 C

Heat rejection i
306.92 kW
Air flow
86,505 m³/h
Fans
8 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 86,505 m³/h
External surface 918.5 m²
Inner volume 129.6 dm³
Fin materialAluminium
Net weight 736 kg
Fans
Quantity 8
Diameter 630 mm
Speed 1,330 rpm
Power 10,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2X463BD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
306.915 kW Fluid flow 53.27 m³/h Pressure drop 78.0 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
252.380 kW Fluid flow 43.77 m³/h Pressure drop 55.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 181.16 not rated not rated not rated not rated not rated
40 306.92 181.56 not rated not rated not rated not rated
45 429.34 306.44 181.94 not rated not rated not rated
50 550.72 428.11 306.10 182.33 not rated not rated
55 671.61 548.76 427.11 305.89 182.81 not rated
60 792.20 668.93 547.17 426.48 306.02 183.46

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 150.05 not rated not rated not rated not rated not rated
40 252.38 150.55 not rated not rated not rated not rated
45 351.83 252.24 150.99 not rated not rated not rated
50 450.33 351.16 252.18 151.45 not rated not rated
55 548.39 449.17 350.69 252.26 151.87 not rated
60 646.19 546.76 448.31 350.46 252.38 152.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 306.915 53.27 78.0
Low speed (Y) 252.380 43.77 55.1

Dimensions

Dimension drawing of BC/BD-2X463BD1-B19 C
Dimension drawing
Dimensions as drawn
A 4050 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 2260 mm
K 4400 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 4050 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.