Skip to Content

Dry cooler BC/BD-2x480NB5-B03 C

Dry cooler BC/BD-2x480NB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-2x480NB5-B03 C

Heat rejection i
306.20 kW
Air flow
85,313 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 85,313 m³/h
External surface 1,671.5 m²
Inner volume 246.8 dm³
Fin materialAluminium
Net weight 1,642 kg
Fans
Quantity 8
Diameter 800 mm
Speed 435 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 73.0 dB(A)
Energy class B
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-2x480NB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
306.196 kW Fluid flow 53.14 m³/h Pressure drop 58.0 kPa
Heat rejection · Low speed (Y)
245.335 kW Fluid flow 42.55 m³/h Pressure drop 39.1 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 182.75 not rated not rated not rated not rated not rated
40 306.20 182.65 not rated not rated not rated not rated
45 426.57 305.14 182.56 not rated not rated not rated
50 545.97 424.63 304.22 182.49 not rated not rated
55 664.93 543.18 422.95 303.42 182.41 not rated
60 783.61 661.28 540.76 421.53 302.74 182.52

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.56 not rated not rated not rated not rated not rated
40 245.34 147.25 not rated not rated not rated not rated
45 340.52 244.05 146.96 not rated not rated not rated
50 434.85 338.37 242.95 146.81 not rated not rated
55 528.80 431.85 336.50 242.16 146.81 not rated
60 622.52 524.96 429.26 335.14 241.72 146.97

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 306.196 53.14 58.0
Low speed (Y) 245.335 42.55 39.1

Dimensions

Dimension drawing of BC/BD-2x480NB5-B03 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 2360 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 2310 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 2360 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.